2427883 – FLUKE-1503 Insulation Tester -FLUKE

713.72$ VAT included

Out of stock

SKU: acac642c85a0 Category: Brand:

Description

Category: Insulation Tester
Product Name: FLUKE-1503 Insulation Tester
Brand: FLUKE
Packing Condition: Packed

Additional information

Weight 1.375 kg
CATEGORY

RANGE

1000 V / 2 GOhm

VOLTAGE

1000 V

RESISTANCE

2 GOhm

MODEL

FLUKE-1503

BRAND

Specification

Specifications: Fluke 1503 Insulation Resistance Meter
AC/DC Voltage Measurement
Accuracy Range 600.0 V
Resolution 0.1 V
50 Hz to 400 Hz ±(% of Rdg + Digits) ±(2% + 3)
Input impedance 3 MΩ (nominal), < 100 pF
Common mode rejection ratio (1 kΩ unbalanced) > 60 dB at DC, 50 or 60 Hz
Overload protection 600 V rms or DC
Earth Bond Resistance Measurement
Range/Resolution 20.00 Ω 0.01 Ω
200.0 Ω 0.1 Ω
2000 Ω 1.0 Ω
20.00 kΩ 0.01 kΩ
Accuracy ±(1.5% + 3)
Overload protection 2 V rms or DC
Open circuit test voltage > 4.0 V, < 8 V
Short circuit current > 200.0 mA
Insulation Specifications
Measurement range 0.01 MΩ to 2000 MΩ
Test voltage 500 V, 1000 V
Test voltage accuracy + 20%, – 0%
Short circuit current 1 mA nominal
Auto discharge Discharge time < 0.5 second for C = 1 µF or less
Live circuit indicator Inhibit test if terminal voltage > 30 V prior to initialization of test
Maximum capacitive load Operable with up to 1 µF load
Measure accuracy
500 V ±(1.5% + 5)
1000 V ±(1.5% + 5) to 2000 MΩ, ±(10% + 3) above 2000 MΩ
General Specifications
Maximum voltage applied to any terminal: 600 V AC rms or DC
Storage temperature -40°C to 60°C (-40°F to 140°F)
Operating temperature -20°C to 55°C (-4°F to 131°F)
Temperature coefficient 0.05 x (specified accuracy) per °C for temperatures < 18°C or > 28°C (< 64°F or > 82°F)
Relative humidity
0% to 95% @ 10°C to 30°C (50°F to 86°F)
0% to 75% @ 30°C to 40°C (86°F to 104°F)
0% to 40% @ 40°C to 55°C (104°F to 131°F)
Vibration Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument
Shock 1 meter drop per IEC 61010-1 2nd Edition (1 meter drop test, six sides, oak floor)
Electromagnetic compatibility In an RF field of 3 V/M, accuracy = specified accuracy (EN 61326-1:1997)
Safety Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement category IV 600 V (CAT IV)
Certifications CSA per standard CSA/CAN C22.2 No. 61010.1-04; TUV per standard IEC/EN 61010-1 2nd Edition
Batteries Four AA batteries (NEDA 15A or IEC LR6)
Battery llife Insulation test use: Tester can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off.
Resistance measurements: Tester can perform at least 2500 earth bond resistance measurements with fresh alkaline batteries at room temperature. These are standard tests of 1 Ω with a duty cycle of 5 seconds on and 25 seconds off.
Size (H x W x L) 5.0 x 10.0 x 20.3 cm (1.97 x 3.94 x 8.00 in)
Weight 550 g (1.2 lb)
IP rating IP40
Altitude Operating 2000 m CAT IV 600 V, 3000 m CAT III 600 V
Non-operating (storage) 12,000 m
Over-range capability 110% of range
Included accessories TL224 Test Leads, TP74 Test Probes, clips PN 1958654 (red) and PN 1958646 (black), holster and remote probe

Download

Video

Reviews

There are no reviews yet.

Be the first to review “2427883 – FLUKE-1503 Insulation Tester -FLUKE”

Your email address will not be published. Required fields are marked *